# 注意:所用 " , " 为分割符号,所有翻译不要用逗号 # 告警key,告警等级(1:一级告警,2:二级告警,3:三级告警,4:故障,5:外部故障),中文,英文 # EMS告警信息 A_EMS_UNSTART,3,EMS未启动,EMS not started A_EMS_HARDWAREALARM_PHY_PORT_ERROR,4,网口异常,Physical Port Error A_EMS_HARDWAREALARM_CAN_PORT_ERROR,4,CAN口异常,CAN Port Error A_EMS_HARDWAREALARM_RS485_PORT_ERROR,4,RS485口异常,RS485 Port Error A_EMS_HARDWAREALARM_DI_PORT_ERROR,4,DI口异常,DI Port Error A_EMS_HARDWAREALARM_DO_PORT_ERROR,4,DO口异常,DO Port Error A_EMS_HARDWAREALARM_4G_PORT_ERROR,4,4G模块异常,4G Module Error A_EMS_HARDWAREALARM_SIM_CARD_ERROR,4,SIM卡异常,SIM Card Error A_EMS_HARDWAREALARM_SSD_DISK_ERROR,4,SSD模块异常,SSD Module Error A_EMS_HARDWAREALARM_TF_CARD_ERROR,4,TF卡模块异常,TF Card Module Error A_EMS_HARDWAREALARM_DC24V_POWER_ERROR,4,DC24V电源异常,DC 24V Power Error A_EMS_HARDWAREALARM_RTC_ERROR,4,RTC时钟异常,RTC Clock Error A_EMS_HARDWAREALARM_NTC_SENSOR_ANOMALY,4,NTC传感器异常,NTC Sensor Anomaly A_EMS_HARDWAREALARM_ADC_SENSOR_ANOMALY,4,ADC采样异常,ADC Sampling Anomaly A_EMS_SYSTEMALARM_APPLICATION_TERMINATION,2,应用程序退出,Application Termination A_EMS_SYSTEMALARM_CONFIG_FILE_LOSS,2,配置文件丢失,Configuration File Lost A_EMS_SYSTEMALARM_CONFIG_PARA_ERROR,2,配置错误,Configuration Parameter Error A_EMS_SYSTEMALARM_LOG_STORAGE_EXCEPTION,2,日志存储异常,Log Storage Exception A_EMS_SYSTEMALARM_FORCE_CONTRL,2,强控模式开启,Force Control Mode Enabled A_EMS_SYSTEMALARM_UPGRADE_FAIL,2,升级失败,Upgrade Failed A_EMS_SYSTEMALARM_CLOUD_TIME_DESYNCHRONIZATION,2,云时间不同步,Cloud Time Desynchronization A_EMS_SYSTEMALARM_SHM_MEMORY_NULL,2,共享内存为空,Shared Memory Null A_EMS_SYSTEMALARM_CELL_CHARGE_TEMP_HIGH,2,电池充电高温保护,Cell Charge Temp High A_EMS_SYSTEMALARM_CELL_CHARGE_TEMP_LOW,2,电池充电低温保护,Cell Charge Temp Low A_EMS_SYSTEMALARM_CELL_DISCHARGE_TEMP_HIGH,2,电池放电高温保护,Cell DisCharge Temp High A_EMS_SYSTEMALARM_CELL_DISCHARGE_TEMP_LOW,2,电池放电低温保护,Cell DisCharge Temp Low A_EMS_SYSTEMALARM_CELL_CHARGE_VOLTE_HIGH,2,电池充电电压保护,Cell Charge Volte High A_EMS_SYSTEMALARM_CELL_DISCHARGE_VOLTE_LOW,2,电池放电电压保护,Cell DisCharge Volte Low A_EMS_SYSTEMALARM_EMS_EMERGENCY_STOP,2,急停(EPO),Emergency Power Off A_EMS_SYSTEMALARM_LOGICAL_ANOMALY,2,逻辑错误,Logical Anomaly A_EMS_EXTDEVALARM_CIRCUIT_BREAKER_ANOMALY,4,电网端口断路器异常,Circuit Breaker Anomaly A_EMS_EXTDEVALARM_DIESEL_GENERATOR_BREAKER_ANOMALY,4,柴发端口断路器异常,Diesel Generator Breaker Anomaly # PMS告警信息 注意PMS和EMS使用了同一份报警码 除了 EMS未启动 告警 A_PMS_OFFINE,4,PMS离线,Offline # BMS告警信息 A_BMS_STACK_OFFINE,4,电池离线,Offline #BMS 一级告警 A_BMS_ALARM_I_CELL_VOLT_HIGH,1,单体电压高,High Cell Voltage A_BMS_ALARM_I_CELL_VOLT_LOW,1,单体电压低,Low Cell Voltage A_BMS_ALARM_I_CELL_VOLT_DIFF_HIGH,1,单体压差大,Excessive Cell Voltage Deviation A_BMS_ALARM_I_TOTAL_VOLT_HIGH,1,总压高,High Total Voltage A_BMS_ALARM_I_TOTAL_VOLT_LOW,1,总压低,Low Total Voltage A_BMS_ALARM_I_TEMP_RISE_FAST,1,温升告警,Rapid Temperature Rise Alarm A_BMS_ALARM_I_CHARGE_TEMP_HIGH,1,充电温度高,High Temp During Charge A_BMS_ALARM_I_CHARGE_TEMP_LOW,1,充电温度低,Low Temp During Charge A_BMS_ALARM_I_CELL_TEMP_DIFF_HIGH,1,温差大,Cell Temp. Diff. High A_BMS_ALARM_I_DISCHARGE_TEMP_HIGH,1,放电温度高,High Temp During Discharge A_BMS_ALARM_I_DISCHARGE_TEMP_LOW,1,放电温度低,Low Temp During Discharge A_BMS_ALARM_I_CHARGE_CURRENT_HIGH,1,充电电流大,High Charge Current A_BMS_ALARM_I_DISCHARGE_CURRENT_HIGH,1,放电电流大,High Discharge Current A_BMS_ALARM_I_INSULATION_LOW,1,绝缘低,Low Insulation Resistance A_BMS_ALARM_I_PACK_VOLT_HIGH,1,电池包总压高,High Pack Voltage A_BMS_ALARM_I_PACK_VOLT_LOW,1,电池包总压低,Low Pack Voltage A_BMS_ALARM_I_SOC_HIGH,1,簇SOC高,High Cluster State of Charge A_BMS_ALARM_I_SOC_LOW,1,簇SOC低,Low Cluster State of Charge A_BMS_ALARM_I_SOE_HIGH,1,簇SOE高,High Cluster State of Energy A_BMS_ALARM_I_SOE_LOW,1,簇SOE低,Low Cluster State of Energy A_BMS_ALARM_I_CLUSTER_VOLT_DIFF_HIGH,1,簇间压差大,Excessive Cluster Voltage Deviation A_BMS_ALARM_I_CLUSTER_CURRENT_DIFF_HIGH,1,簇间电流大,High Inter-Cluster Current A_BMS_ALARM_I_CLUSTER_CHARGE_CURRENT_HIGH,1,簇充电电流大,High Cluster Charge Current A_BMS_ALARM_I_CLUSTER_DISCHARGE_CURRENT_HIGH,1,簇放电电流大,High Cluster Discharge Current A_BMS_ALARM_I_CLUSTER_CIRCULATION_HIGH,1,簇间环流高,High Inter-Cluster Circulating Current A_BMS_ALARM_I_PACK_POLE_TEMP_HIGH,1,包极柱温度高,High Battery Terminal Temperature A_BMS_ALARM_I_THERMORUNAWAY_ALARM,1,热失控告警,Thermal Runaway Alarm #BMS 二级告警 A_BMS_ALARM_II_CELL_VOLT_HIGH,2,单体电压高,High Cell Voltage A_BMS_ALARM_II_CELL_VOLT_LOW,2,单体电压低,Low Cell Voltage A_BMS_ALARM_II_CELL_VOLT_DIFF_HIGH,2,单体压差大,Excessive Cell Voltage Deviation A_BMS_ALARM_II_TOTAL_VOLT_HIGH,2,总压高,High Total Voltage A_BMS_ALARM_II_TOTAL_VOLT_LOW,2,总压低,Low Total Voltage A_BMS_ALARM_II_TEMP_RISE_FAST,2,温升告警,Rapid Temperature Rise Alarm A_BMS_ALARM_II_CHARGE_TEMP_HIGH,2,充电温度高,High Temp During Charge A_BMS_ALARM_II_CHARGE_TEMP_LOW,2,充电温度低,Low Temp During Charge A_BMS_ALARM_II_CELL_TEMP_DIFF_HIGH,2,温差大,Cell Temp. Diff. High A_BMS_ALARM_II_DISCHARGE_TEMP_HIGH,2,放电温度高,High Temp During Discharge A_BMS_ALARM_II_DISCHARGE_TEMP_LOW,2,放电温度低,Low Temp During Discharge A_BMS_ALARM_II_CHARGE_CURRENT_HIGH,2,充电电流大,High Charge Current A_BMS_ALARM_II_DISCHARGE_CURRENT_HIGH,2,放电电流大,High Discharge Current A_BMS_ALARM_II_INSULATION_LOW,2,绝缘低,Low Insulation Resistance A_BMS_ALARM_II_PACK_VOLT_HIGH,2,电池包总压高,High Pack Voltage A_BMS_ALARM_II_PACK_VOLT_LOW,2,电池包总压低,Low Pack Voltage A_BMS_ALARM_II_SOC_HIGH,2,簇SOC高,High Cluster State of Charge A_BMS_ALARM_II_SOC_LOW,2,簇SOC低,Low Cluster State of Charge A_BMS_ALARM_II_SOE_HIGH,2,簇SOE高,High Cluster State of Energy A_BMS_ALARM_II_SOE_LOW,2,簇SOE低,Low Cluster State of Energy A_BMS_ALARM_II_CLUSTER_VOLT_DIFF_HIGH,2,簇间压差大,Excessive Cluster Voltage Deviation A_BMS_ALARM_II_CLUSTER_CURRENT_DIFF_HIGH,2,簇间电流大,High Inter-Cluster Current A_BMS_ALARM_II_CLUSTER_CHARGE_CURRENT_HIGH,2,簇充电电流大,High Cluster Charge Current A_BMS_ALARM_II_CLUSTER_DISCHARGE_CURRENT_HIGH,2,簇放电电流大,High Cluster Discharge Current A_BMS_ALARM_II_CLUSTER_CIRCULATION_HIGH,2,簇间环流高,High Inter-Cluster Circulating Current A_BMS_ALARM_II_PACK_POLE_TEMP_HIGH,2,包极柱温度高,High Battery Terminal Temperature A_BMS_ALARM_II_THERMORUNAWAY_ALARM,2,热失控告警,Thermal Runaway Alarm #BMS 三级告警 A_BMS_ALARM_III_CELL_VOLT_HIGH,3,单体电压高,High Cell Voltage A_BMS_ALARM_III_CELL_VOLT_LOW,3,单体电压低,Low Cell Voltage A_BMS_ALARM_III_CELL_VOLT_DIFF_HIGH,3,单体压差大,Excessive Cell Voltage Deviation A_BMS_ALARM_III_TOTAL_VOLT_HIGH,3,总压高,High Total Voltage A_BMS_ALARM_III_TOTAL_VOLT_LOW,3,总压低,Low Total Voltage A_BMS_ALARM_III_TEMP_RISE_FAST,3,温升告警,Rapid Temperature Rise Alarm A_BMS_ALARM_III_CHARGE_TEMP_HIGH,3,充电温度高,High Temp During Charge A_BMS_ALARM_III_CHARGE_TEMP_LOW,3,充电温度低,Low Temp During Charge A_BMS_ALARM_III_CELL_TEMP_DIFF_HIGH,3,温差大,Cell Temp. Diff. High A_BMS_ALARM_III_DISCHARGE_TEMP_HIGH,3,放电温度高,High Temp During Discharge A_BMS_ALARM_III_DISCHARGE_TEMP_LOW,3,放电温度低,Low Temp During Discharge A_BMS_ALARM_III_CHARGE_CURRENT_HIGH,3,充电电流大,High Charge Current A_BMS_ALARM_III_DISCHARGE_CURRENT_HIGH,3,放电电流大,High Discharge Current A_BMS_ALARM_III_INSULATION_LOW,3,绝缘低,Low Insulation Resistance A_BMS_ALARM_III_PACK_VOLT_HIGH,3,电池包总压高,High Pack Voltage A_BMS_ALARM_III_PACK_VOLT_LOW,3,电池包总压低,Low Pack Voltage A_BMS_ALARM_III_SOC_HIGH,3,簇SOC高,High Cluster State of Charge A_BMS_ALARM_III_SOC_LOW,3,簇SOC低,Low Cluster State of Charge A_BMS_ALARM_III_SOE_HIGH,3,簇SOE高,High Cluster State of Energy A_BMS_ALARM_III_SOE_LOW,3,簇SOE低,Low Cluster State of Energy A_BMS_ALARM_III_CLUSTER_VOLT_DIFF_HIGH,3,簇间压差大,Excessive Cluster Voltage Deviation A_BMS_ALARM_III_CLUSTER_CURRENT_DIFF_HIGH,3,簇间电流大,High Inter-Cluster Current A_BMS_ALARM_III_CLUSTER_CHARGE_CURRENT_HIGH,3,簇充电电流大,High Cluster Charge Current A_BMS_ALARM_III_CLUSTER_DISCHARGE_CURRENT_HIGH,3,簇放电电流大,High Cluster Discharge Current A_BMS_ALARM_III_CLUSTER_CIRCULATION_HIGH,3,簇间环流高,High Inter-Cluster Circulating Current A_BMS_ALARM_III_PACK_POLE_TEMP_HIGH,3,包极柱温度高,High Battery Terminal Temperature A_BMS_ALARM_III_THERMORUNAWAY_ALARM,3,热失控告警,Thermal Runaway Alarm #CBMS 保护故障 A_CBMS_ALARM_CELL_VOLT_FAULT,4,单体电压故障,Cell Voltage Fault A_CBMS_ALARM_TEMPSENSOR_OPEN_CIRCUIT,4,温度开路,Temperature Sensor Open Circuit A_CBMS_ALARM_TEMPSENSOR_SHORT_CIRCUIT,4,温度短路,Temperature Sensor Short Circuit A_CBMS_ALARM_BALANCE_ERROR,4,均衡故障,Balancing Fault A_CBMS_ALARM_HARDWARE_ERROR,4,硬件故障,Hardware Fault A_CBMS_ALARM_CELL_STATIC_ERROR,4,单体静态不变故障,Static Cell Voltage Fault A_CBMS_ALARM_CELL_EXTRI_HIGH,4,单体极高,Extremely High Cell Voltage A_CBMS_ALARM_TEMP_EXTRI_HIGH,4,温度极高,Extremely High Temperature A_CBMS_ALARM_CELL_EXTRI_LOW,4,单体极低,Extremely Low Cell Voltage A_CBMS_ALARM_CELL_HOP_FREQUENTLY,4,单体电压跳变,single cell voltage jump A_CBMS_ALARM_CELL_TEMP_STATIC,4,单体温度静止不变,Static Temperature Fault A_CBMS_ALARM_CELL_TEMP_JUMP,4,单体温度跳变,Temperature Jump A_CBMS_ALARM_CLUSTER_TOTAL_VOLT_ABNORMAL,4,簇总压异常,Cluster Total Voltage Anomaly A_CBMS_ALARM_HVM_COMMUNICATION_ABNORMAL,4,HVM通信异常,HVM Communication Failure A_CBMS_ALARM_ABMS_COMMUNICATION_FAULT,4,ABMS通信故障,ABMS Communication Fault A_CBMS_ALARM_PACK_COMMUNICATION_FAULT,4,PACK通信故障,Pack Communication Fault A_CBMS_ALARM_CIRCUIT_BREAKER_FAULT,4,断路器故障,Circuit Breaker Fault A_CBMS_ALARM_MAIN_POSTIVE_RELAY_FAULT,4,主正继电器故障,Main Positive Relay Fault A_CBMS_ALARM_MAIN_NEGATIVE_RELAY_FAULT,4,主负继电器故障,Main Negative Relay Fault A_CBMS_ALARM_CURRENT_ABNORMAL,4,电流异常,Current Anomaly A_CBMS_ALARM_CURRENT_LIMIT_ABNORMAL,4,限流异常,Current Limiting Failure A_CBMS_ALARM_FUSES_FAULT,4,熔丝故障,Fuse Fault A_CBMS_ALARM_SHORT_CIRCUIT_CURRENT,4,电流短路,Current Short Circuit A_CBMS_ALARM_FAN_FAULT,4,风扇故障,Fan Fault A_CBMS_ALARM_INTERNAL_ABNORMAL,4,CBMS内部异常,CBMS Internal Error #ABMS保护故障 A_ABMS_ALARM_CLUSTER_COMMUNICATION_ABNORMAL,4,与簇通讯异常,Cluster Communication Failure A_ABMS_ALARM_ABMS_FAN_FAULT,4,ABMS控制风扇故障,ABMS Cooling Fan Control Fault A_ABMS_ALARM_ABMS_BREAKER_FAULT,4,ABMS断路器故障,ABMS Circuit Breaker Fault A_ABMS_ALARM_CLUSTER_NUMBER_INSUFFICAL,4,电池簇就位数量不足,Insufficient Cluster Mounting A_ABMS_ALARM_CLUSTER_NUMBER_EXCEED,4,电池簇就位数量超出,Excessive Cluster Mounting A_ABMS_ALARM_ABMS_CURRENT_LOOP_FAULT,4,ABMS电流环故障,ABMS Current Loop Anomaly A_ABMS_ALARM_TOTAL_VOLT_INVALID,4,总压采集无效,Total Voltage Sampling Invalid A_ABMS_ALARM_TEMPERATURE_INVALID,4,温度采集无效,Temperature Sampling Invalid A_ABMS_ALARM_ABMS_HVM_COMMUNICATION_ABNORMAL,4,ABMS高压板通讯异常,ABMS High-Voltage Board Comm Fault A_ABMS_ALARM_CURRENT_LIMIT_FAULT,4,限流失败,Current Limiting Failure A_ABMS_ALARM_24V_POWER_VOLT_ABNORMAL,4,24V供电电压异常,24V Power Supply Anomaly A_ABMS_ALARM_BAU_HARDWARE_ABNORMAL,4,BAU硬件异常,BAU Hardware Fault A_ABMS_ALARM_INTERNAL_FAULT_ALL,4,ABMS内部异常,ABMS Internal Error #BMS外设故障 A_BMS_PERIPHERAL_EMERGENCY_STOP,5,触发急停,Emergency Stop Triggered A_BMS_PERIPHERAL_PCS_COMMUNICATION_FAILED,5,与PCS通讯失败,PCS Communication Failure A_BMS_PERIPHERAL_EMS_COMMUNICATION_FAILED,5,与EMS通讯失败,EMS Communication Failure A_BMS_PERIPHERAL_FIRE_SYSTEM_ANOMALY,5,消防设备通讯异常,Fire equipment communication failure A_BMS_PERIPHERAL_LIQUID_COOLING_UNIT_ANOMALY,5,液冷机设备通讯异常,Liquid cooling equipment communication failure A_BMS_PERIPHERAL_AIR_CONDITIONER_ANOMALY,5,空调设备通讯异常,Air conditioning equipment communication failure A_BMS_PERIPHERAL_WATER_LEAKAGE_ANOMALY,5,水浸设备通讯异常,Water immersion equipment communication failure A_BMS_PERIPHERAL_SMOKE_DETECTOR_ANOMALY,5,烟感设备通讯异常,Smoke detector equipment communication failure A_BMS_PERIPHERAL_COMBUSTIBLE_GAS_ANOMALY,5,可燃气体设备通讯异常,Combustible gas equipment communication failure A_BMS_PERIPHERAL_UPS_ANOMALY,5,UPS设备通讯异常,UPS equipment communication failure A_BMS_PERIPHERAL_FIRE_ALARM_WARNING,5,火警告警,Fire Alarm A_BMS_PERIPHERAL_FIRE_ALARM_ACTIVATION,5,火警动作,Fire Alarm Action A_BMS_PERIPHERAL_DC_LIGHTNING_PROTECTION_FAULT,5,DC防雷故障,DC SPD Fault A_BMS_PERIPHERAL_AC_LIGHTNING_PROTECTION_FAULT,5,AC防雷故障,AC SPD Fault A_BMS_PERIPHERAL_UPS_DISCHARGE_COMPLETE,5,UPS电量放空,UPS Battery Depleted A_BMS_PERIPHERAL_SMOKE_DETECTOR_ALARM,5,烟感报警,Smoke Detection Alarm A_BMS_PERIPHERAL_CO_CONCENTRATION_HIGH,5,CO浓度过高,High CO Concentration A_BMS_PERIPHERAL_H2_CONCENTRATION_HIGH,5,H2浓度过高,High H2 Concentration A_BMS_PERIPHERAL_ACCESS_CONTROL_ALERT,5,门禁告警(开门),Access Alert (Door Open) A_BMS_PERIPHERAL_SMOKE_DETECTOR_WARNING,5,烟感触发告警,Smoke Detection Alarm A_BMS_PERIPHERAL_WATER_LEAKAGE_WARNING,5,水浸触发告警,Water Ingress Alarm A_BMS_PERIPHERAL_FIRE_SYSTEM_ALERT,5,消防触发告警,Fire Protection Manual Alarm A_BMS_PERIPHERAL_LIGHTNING_STRIKE_ALERT,5,雷击触发告警,Lightning Strike Alarm A_BMS_PERIPHERAL_STORAGE_PRESSURE_WARNING,5,气瓶压力触发告警,Extinguisher Cylinder Pressure Alert A_BMS_PERIPHERAL_GRID_POWER_OUTAGE_OCCUR,5,市电断电触发,Grid Power Failure Trigger A_BMS_PERIPHERAL_HEATER_ANOMALY,5,加热器异常,Heater Fault A_BMS_PERIPHERAL_DEHUMIDIFIER_ANOMALY,5,除湿器异常,Dehumidifier Fault #BMS 风冷空调 A_AIRCOOL_HIGH_TEMP_ALARM,5,高温告警(风冷),High Temp Alarm (Air-Cooled) A_AIRCOOL_LOW_TEMP_ALARM,5,低温告警(风冷),Low Temp Alarm (Air-Cooled) A_AIRCOOL_COIL_ANTI_FREEZE,5,盘管防冻(风冷),Coil Freeze Protection (Air-Cooled) A_AIRCOOL_DISCHARGE_HIGH_TEMP,5,排气高温(风冷),Discharge Overheat (Air-Cooled) A_AIRCOOL_COIL_TEMP_SENSOR_FAIL,5,盘管温感失效(风冷),Coil Temp Sensor Failure (Air-Cooled) A_AIRCOOL_OUTDOOR_TEMP_SENSOR_FAIL,5,室外温感失效(风冷),Ambient Temp Sensor Failure (Air-Cooled) A_AIRCOOL_CONDENSER_TEMP_SENSOR_FAIL,5,冷凝温感失效(风冷),Condenser Temp Sensor Failure (Air-Cooled) A_AIRCOOL_INDOOR_TEMP_SENSOR_FAIL,5,内温感失效(风冷),Room Temp Sensor Failure (Air-Cooled) A_AIRCOOL_INDOOR_FAN_FAULT,5,内风机故障(风冷),Indoor Fan Failure (Air-Cooled) A_AIRCOOL_OUTDOOR_FAN_FAULT,5,外风机故障(风冷),Outdoor Fan Failure (Air-Cooled) A_AIRCOOL_COMPRESSOR_FAULT,5,压缩机故障(风冷),Compressor Fault (Air-Cooled) A_AIRCOOL_ELECTRIC_HEATER_FAULT,5,电加热故障(风冷),Heater Bank Fault (Air-Cooled) A_AIRCOOL_HIGH_PRESSURE_ALARM,5,高压告警(风冷),High Pressure Alarm (Air-Cooled) A_AIRCOOL_HIGH_PRESSURE_LOCKOUT,5,高压锁定(风冷),High Pressure Lockout (Air-Cooled) A_AIRCOOL_DISCHARGE_LOCKOUT,5,排气锁定(风冷),Discharge Lockout (Air-Cooled) A_AIRCOOL_AC_OVER_VOLTAGE,5,交流过压(风冷),AC Over-Voltage (Air-Cooled) A_AIRCOOL_AC_UNDER_VOLTAGE,5,交流欠压(风冷),AC Under-Voltage (Air-Cooled) A_AIRCOOL_AC_POWER_LOSS,5,交流掉电(风冷),AC Power Loss (Air-Cooled) A_AIRCOOL_PHASE_LOSS,5,缺相(风冷),Phase Loss (Air-Cooled) A_AIRCOOL_FREQUENCY_ABNORMAL,5,频率异常(风冷),Frequency Deviation (Air-Cooled) A_AIRCOOL_PHASE_REVERSE,5,逆相(风冷),Phase Reversal (Air-Cooled) #BMS 液冷 A_LIQUIDCOOL_HIGH_TEMP_OUTLET_WATER,5,出水温度高(液冷),High Temp Outlet Water (Liquid-Cooled) A_LIQUIDCOOL_LOW_TEMP_OUTLET_WATER,5,出水温度低(液冷),Low Temp Outlet Water (Liquid-Cooled) A_LIQUIDCOOL_OUTLET_WATER_TEMP_SENSOR_FAULT,5,出水温度传感器故障(液冷),Outlet Water Temperature Sensor Fault (Liquid-Cooled) A_LIQUIDCOOL_RETURN_WATER_TEMP_SENSOR_FAULT,5,回水温度传感器故障(液冷),Return Water Temperature Sensor Fault (Liquid-Cooled) A_LIQUIDCOOL_COIL_ANTI_FREEZE,5,盘管防冻(液冷),Coil Freeze Protection (Liquid-Cooled) A_LIQUIDCOOL_DISCHARGE_HIGH_TEMP,5,排气高温(液冷),Discharge Overheat (Liquid-Cooled) A_LIQUIDCOOL_OTHER_TEMP_SENSOR_FAULT,5,其他温度传感器故障(液冷),Other Temp Sensor Fault (Liquid-Cooled) A_LIQUIDCOOL_COMMUNICATION_FAULT,5,通讯故障(液冷),Communication Failure (Liquid-Cooled) A_LIQUIDCOOL_FAN_FAULT,5,风机故障(液冷),Fan Fault (Liquid-Cooled) A_LIQUIDCOOL_WATER_PUMP_ABNORMALITY,5,水泵异常(液冷),Water Pump Abnormality (Liquid-Cooled) A_LIQUIDCOOL_COMPRESSOR_FAULT,5,压缩机故障(液冷),Compressor Lockout (Liquid-Cooled) A_LIQUIDCOOL_ELECTRIC_HEATER_FAULT,5,电加热故障(液冷),Heater Bank Failure (Liquid-Cooled) A_LIQUIDCOOL_LOW_WATER_LEVEL_ALARM,5,缺水告警(液冷),Low Water Level Alarm (Liquid-Cooled) A_LIQUIDCOOL_WATER_RESSURE_ABNORMALITY,5,水压异常(液冷),Water Pressure Abnormality (Liquid-Cooled) A_LIQUIDCOOL_INVERTER_ABNORMALITY,5,变频器异常(液冷),Inverter Abnormality (Liquid-Cooled) A_LIQUIDCOOL_MAKE_UP_WATER_TANK_LOW_WATER_LEVEL,5,补水箱低水位(液冷),Make Up Water Tank Low Water Level (Liquid-Cooled) A_LIQUIDCOOL_HIGH_PRESSURE_LOCKOUT,5,高压锁定(液冷),High Pressure Lockout (Liquid-Cooled) A_LIQUIDCOOL_LOW_PRESSURE_LOCKOUT,5,低压锁定(液冷),Low Pressure Lockout (Liquid-Cooled) A_LIQUIDCOOL_EXHAUST_ABNORMALITY,5,排气异常(液冷),Exhaust Abnormality (Liquid-Cooled) A_LIQUIDCOOL_AC_POWER_SUPPLY_ABNORMALITY,5,交流电源异常(液冷),AC Power Supply Abnormality (Liquid-Cooled) A_LIQUIDCOOL_OTHER_FAULT,5,其他故障(液冷),General System Fault (Liquid-Cooled) #BMS 消防设备 A_FIRE_FIGHTING_DEVICE_COMM_FAULT,5,设备通讯故障(消防),Communication Failure (Fire Protection) A_FIRE_FIGHTING_DEVICE_FAILURE,5,设备失效(消防),Equipment Failure (Fire Protection) A_FIRE_FIGHTING_PRODUCT_EXPIRED,5,产品过期(消防),Product Expiration (Fire Protection) A_FIRE_FIGHTING_DEVICE_OVER_VOLTAGE,5,设备过压(消防),Overvoltage (Equipment) (Fire Protection) A_FIRE_FIGHTING_DEVICE_UNDER_VOLTAGE,5,设备欠压(消防),Undervoltage (Equipment) (Fire Protection) A_FIRE_FIGHTING_FIRE_ALARM,5,火警(消防),Fire Alarm (Fire Protection) A_FIRE_FIGHTING_WATER_LEAKAGE_ALARM,5,水浸(消防),Water Immersion Alarm (Fire Protection) # PCS告警信息 A_PCS_OFFLINE,4,离线,Offline #PCS 告警码-HW硬件 A_PCS_ALARM_HW_AC_MODULE_ALARM,2,AC模块告警,AC Module Alarm A_PCS_ALARM_HW_RACK_FUNC_BOARD_ALARM,2,机架功能板告警,Rack Function Board Alarm A_PCS_ALARM_HW_OVERLOAD_ALARM,2,模块过载报警,Module Overload Alarm A_PCS_ALARM_HW_CALIBRATION_PARAMETER_ABNORMAL,2,校准参数异常,Calibration Parameter Abnormality A_PCS_ALARM_HW_OTHER_ALARM,2,其他告警,Other Alarm #PCS 故障码-HW硬件 A_PCS_FAULT_HW_EPO_EMERGENCY_POWER_OFF,4,Emergency Power Off(EPO)故障,Emergency Power Off(EPO) A_PCS_FAULT_HW_IGBT_OCP_OVER_CURRENT_PROTECTION,4,IGBT 过流保护(OCP) 故障,IGBT Overcurrent Protection (OCP) fault A_PCS_FAULT_HW_BUSBAR_HARDWARE_OVER_VOLT,4,母线硬件过压故障,Bus Hardware Overvoltage Fault A_PCS_FAULT_HW_POWER_MODULE_CYCLE_BY_CYCLE_CURRENT_LIMIT,4,功率模块逐波限流故障,Power Module Wave-by-Wave Current Limiting Fault A_PCS_FAULT_HW_BALANCE_MODULE_CYCLE_BY_CYCLE_CURRENT_LIMIT,4,平衡模块逐波限流故障,Balance Module Wave-by-Wave Current Limiting Fault A_PCS_FAULT_HW_FUSE_BLOWN,4,保险故障,Fuse or protection device fault A_PCS_FAULT_HW_AC_MODULE_FAULT,4,AC模块故障,AC module malfunction A_PCS_FAULT_HW_RACK_FUNC_BOARD_FAULT,4,机架功能板故障,Rack function board malfunction A_PCS_FAULT_HW_MAIN_BOARD_HW_FAULT,4,控制板硬件故障,Control board hardware malfunction A_PCS_FAULT_HW_SAMPLING_ZERO_ABNORMAL,4,AD 零漂过大故障,AD Zero Drift Excessive Fault A_PCS_FAULT_HW_DRY_CONTACT_OVER_TEMPERATURE,4,干接点过温故障,Dry contact overheating fault A_PCS_FAULT_HW_AUXILIARY_POWER_FAULT,4,电源故障,Power Failure A_PCS_FAULT_HW_FAN_FAULT,4,风扇故障,fan failure A_PCS_FAULT_HW_CONNECTION_ERROR,4,连接故障,Connection failure A_PCS_FAULT_HW_INDUCTOR_OVER_TEMPERATURE,4,电感过温故障标志,Inductance over temperature fault sign A_PCS_FAULT_HW_IGBT_MODULE_OVER_TEMPERATURE,4,功率模块过温故障,Power module overheating fault A_PCS_FAULT_HW_BALANCE_MODULE_OVER_TEMPERATURE,4,平衡模块过温故障,Balance module overheating fault A_PCS_FAULT_HW_SYSTEM_FIRE_ALARM,4,系统火警故障,System fire alarm malfunction A_PCS_FAULT_HW_AMBIENT_TEMPERATURE_OVER_TEMPERATURE,4,环境温度过温故障,Ambient Temperature Overhigh Fault A_PCS_FAULT_HW_AMBIENT_HUMIDITY_TOO_HIGH,4,环境湿度过高,Environmental Humidity Overhigh Fault A_PCS_FAULT_HW_TRANSFORMER_OVER_TEMP,4,变压器过温,Transformer overheating A_PCS_FAULT_HW_HARDWARE_SAMPLING_ABNORMAL,4,硬件采样异常,Hardware sampling exception A_PCS_FAULT_HW_MODULE_CURRENT_ASYMMETRIC,4,模块电流不平衡,Module current imbalance A_PCS_FAULT_HW_REVERSE_POLARITY_OF_PV_COMPONENT,4,PV极性反接,PV Reverse Polarity A_PCS_FAULT_HW_DETECT_FAULTS_OF_DC_FUSES,4,检测熔断器故障,Fuse Failure Detection A_PCS_FAULT_HW_CARRIER_SYNCHRONIZATION_FAILURE,4,载波同步故障,Carrier Synchronization Fault A_PCS_FAULT_HW_INTRACAVITARY_TEMPERATURE_IS_TOO_HIGH,4,腔内温度过温,Enclosure Overtemperature A_PCS_FAULT_HW_THERMAL_RADIATOR_TEMPERATURE_DETECTION_FAILURE,4,散热器温度检测故障,Heat Sink Temperature Sensor Fault A_PCS_FAULT_HW_OTHER_FAULT,4,其他硬件故障,Other Hardware Fault #PCS 故障码-AC交流 A_PCS_FAULT_AC_BUS_OVER_VOLT,4,交流母线过压,AC Bus Overvoltage A_PCS_FAULT_AC_BUS_UNDER_VOLT,4,交流母线欠压,AC Bus Undervoltage A_PCS_FAULT_AC_ISLANDING_PROTECTION,4,逆变器孤岛保护,Inverter Anti-Islanding Protection A_PCS_FAULT_AC_BUS_VOLT_ABNORMAL,4,交流母线电压异常,AC Bus Voltage Abnormality A_PCS_FAULT_AC_BUS_OVER_FREQUENCY,4,电网过频故障,Grid Over-Frequency Fault A_PCS_FAULT_AC_BUS_UNDER_FREQUENCY,4,电网欠频故障,Grid Under-Frequency Fault A_PCS_FAULT_AC_PHASE_REVERSED,4,电网相序错误故障,Grid Phase Sequence Error Fault A_PCS_FAULT_AC_PHASE_OVER_CURRENT,4,相过流故障,Phase Overcurrent Fault A_PCS_FAULT_AC_N_LINE_OVER_CURRENT,4,N线过流故障,Neutral Line Overcurrent Fault A_PCS_FAULT_AC_VOLT_IMBALANCE,4,电网电压不平衡故障,Grid Voltage Unbalance Fault A_PCS_FAULT_AC_CURRENT_IMBALANCE,4,电网电流不平衡故障,Grid Current Unbalance Fault A_PCS_FAULT_AC_PHASE_LOST,4,电网缺相故障,Grid Phase Loss Fault A_PCS_FAULT_AC_ACCESS_ABNORMAL,4,电网接入异常,Grid Connection Abnormality A_PCS_FAULT_AC_POWER_DOWN,4,电网掉电,Grid Power Loss A_PCS_FAULT_AC_VOLT_DISTORTION,4,电网电压畸变,Grid Voltage Distortion A_PCS_FAULT_AC_PRE_CHARGE_FAULT,4,交流预充故障,AC Precharge Fault A_PCS_FAULT_AC_LEAKAGE_CURRENT_OVER_CURRENT,4,漏电流过流故障,Leakage Current Overcurrent Fault A_PCS_FAULT_AC_CURRENT_DC_COMPONENT_ABNORMAL,4,交流电流直流分量异常,AC Current DC Offset Abnormality A_PCS_FAULT_AC_OFF_GRID_OUTPUT_SHORT_CIRCUIT,4,离网输出短路故障,Off-Grid Output Short-Circuit Fault A_PCS_FAULT_AC_OFF_GRID_VOLT_PHASE_LOST,4,离网电压缺相,Off-Grid Voltage Phase Loss A_PCS_FAULT_AC_CURRENT_HARMONIC_ABNORMAL,4,交流电流谐波异常,AC Current Harmonic Abnormality A_PCS_FAULT_AC_CONTACTOR_FAULT,4,交流接触器故障,AC Contactor Fault A_PCS_FAULT_AC_PE_N_CONTACTOR_SHORT_CIRCUIT,4,PE接触器故障,PE Contactor Fault A_PCS_FAULT_AC_PE_N_CONTACTOR_OPEN_CIRCUIT,4,N接触器故障,Neutral Contactor Fault A_PCS_FAULT_AC_FREQUENCY_FAULT,4,频率故障,Frequency Fault A_PCS_FAULT_AC_MID_POINT_VOLTAGE_OFFSET,4,中点电压偏移,Neutral-Point Voltage Deviation A_PCS_FAULT_AC_AC_SLOW_START_FAILURE,4,交流软启故障,AC Soft-Start Failure A_PCS_FAULT_AC_UNDER_VOLTAGE_OF_GRID_POWER,4,电网电压欠压,Under-voltage of Grid Power A_PCS_FAULT_AC_OVER_VOLTAGE_OF_GRID_POWER,4,电网电压过压,Over-voltage of Grid Power A_PCS_FAULT_AC_OTHER_FAULT,4,其他交流故障,Other AC Fault #PCS 故障码-DC直流 A_PCS_FAULT_DC_PRE_CHARGE_FAULT,4,直流预充故障,DC Precharge Fault A_PCS_FAULT_DC_INPUT_OVER_VOLT,4,直流过压故障,DC Overvoltage Fault A_PCS_FAULT_DC_INPUT_UNDER_VOLT,4,直流欠压故障,DC Undervoltage Fault A_PCS_FAULT_DC_INPUT_OVER_CURRENT,4,直流过流故障,DC Overcurrent Fault A_PCS_FAULT_DC_RELAY_FAILURE,4,直流继电器故障,DC Relay Fault A_PCS_FAULT_DC_DC_INPUT_REVERSED,4,电池反接,Battery Reverse Polarity A_PCS_FAULT_DC_POSITIVE_AND_NEGATIVE_BUS_UNBALANCED,4,正负母线不平衡,Positive/Negative Bus Imbalance A_PCS_FAULT_DC_BALANCE_MODULE_OVER_CURRENT,4,平衡模块软件过流,Balancing Module Software Overcurrent A_PCS_FAULT_DC_LOW_BATTERY,4,电池电量不足,Battery Low SOC (State of Charge) A_PCS_FAULT_DC_BMS_VOLT_ABNORMAL,4,BMS电压异常,BMS Voltage Abnormality A_PCS_FAULT_DC_BMS_CURRENT_ABNORMAL,4,BMS电流异常,BMS Current Abnormality A_PCS_FAULT_DC_BMS_TEMPERATURE_ABNORMAL,4,BMS温度异常,BMS Temperature Abnormality A_PCS_FAULT_DC_DC_GROUNDING_PROTECTION,4,直流接地保护,DC Grounding Protection A_PCS_FAULT_DC_DC_FUSE_FAILURE,4,直流熔断器故障,DC Fuse Failure A_PCS_FAULT_DC_DC_LEAKAGE_CURRENT_PROTECTION,4,直流漏电流保护,DC Leakage Current Protection A_PCS_FAULT_DC_DC_SLOW_START_FAILURE,4,直流软启故障,DC Slow-Start Failure A_PCS_FAULT_DC_DC_MAIN_CONTACTOR_FAULT,4,直流主接触器故障,DC Main Contactor Fault A_PCS_FAULT_DC_OTHER_FAULT,4,其他直流故障,Other DC Fault #PCS 故障码-Sys系统 A_PCS_FAULT_SYS_MAINBOARD_ERROR,4,主板故障,Mainboard Fault A_PCS_FAULT_SYS_INSULATION_DETECTION_ABNORMAL,4,绝缘检测故障,Insulation Detection Fault A_PCS_FAULT_SYS_EXT_INPUT_DRY_IO,4,外部输入干接点故障,External Dry Contact Fault A_PCS_FAULT_SYS_HARDWARE_VERSION_FAULT,4,硬件版本故障,Hardware Version Mismatch Fault A_PCS_FAULT_SYS_DSP_INITIALIZING_FAULT,4,DSP初始化故障,DSP Initialization Fault A_PCS_FAULT_SYS_SW_AND_FW_MISMATCH,4,软件固件不匹配故障,Firmware Mismatch Fault A_PCS_FAULT_SYS_DATALOG_DATA_FAULT,4,DataLog 数据故障,DataLog Corruption Fault A_PCS_FAULT_SYS_PERIPHERAL_DEVICE_FAILURE,4,外设故障,Peripheral Device Fault A_PCS_FAULT_SYS_PARAMETER_MISMATCH,4,参数不匹配,Parameter Mismatch Fault A_PCS_FAULT_SYS_RESTART_TOO_MUCH,4,重启过多,Excessive Restart Fault A_PCS_FAULT_SYS_SPD_SURGE_PROTECTIVE_DEVICE,4,防雷器SPD故障,SPD (Surge Protective Device) Fault A_PCS_FAULT_SYS_GROUNDING_FAULT,4,接地故障,Ground Fault A_PCS_FAULT_SYS_BMS_SHUTDOWN_FAILURE,4,BMS 关机故障,BMS Shutdown Fault A_PCS_FAULT_SYS_BMS_BATTERY_STATUS_FAULT,4,BMS 电池状态故障,BMS Battery Status Fault A_PCS_FAULT_SYS_BMS_COMMUNICATION_FAILURE,4,CAN通信故障,CAN Communication Fault A_PCS_FAULT_SYS_PCS_INTERNAL_COMMUNICATION_FAILURE,4,PCS 内部通讯故障,PCS Internal Communication Fault A_PCS_FAULT_SYS_EMS_COMMUNICATION_FAILURE,4,外部通信故障,External Communication Fault A_PCS_FAULT_SYS_STS_COMMUNICATION_FAILURE,4,STS 通信故障,STS Communication Fault A_PCS_FAULT_SYS_PARALLEL_SYS_SLAVE_CAN_COMMUNICATION_FAULT,4,并机系统从机CAN通信故障,Parallel System Slave CAN Communication Fault A_PCS_FAULT_SYS_SYSTEM_RESONANCE_FAULT,4,系统谐振故障,System Resonance Fault A_PCS_FAULT_SYS_HIGH_VOLT_RIDE_THROUGH_TIMEOUT,4,高电压穿越超时故障,High Voltage Ride-Through (HVRT) Timeout Fault A_PCS_FAULT_SYS_LOW_VOLT_RIDE_THROUGH_TIMEOUT,4,低电压穿越超时故障,Low Voltage Ride-Through (LVRT) Timeout Fault A_PCS_FAULT_SYS_SYNCHRONOUS_SIGNAL_FAULT,4,同步信号故障,Synchronization Signal Fault A_PCS_FAULT_SYS_SWITCH_ON_OFF_GRID_TOGGLING_ERROR,4,并离网切换错误,Grid-Off-Grid Switching Error A_PCS_FAULT_SYS_OFF_GRID_VOLT_PHASE_REVERSED,4,离网电压反序,Off-Grid Voltage Phase Reversal A_PCS_FAULT_SYS_PLL_FAULT,4,PLL(Phase Locked Loop)锁相失败,PLL (Phase Locked Loop) Lock Failure A_PCS_FAULT_SYS_AUTORUN_FAULT,4,启动故障,Startup Failure A_PCS_FAULT_SYS_FAULT_OF_THE_NEIGHBORING_AIRCRAFT,4,邻机故障,Adjacent Unit Fault A_PCS_FAULT_SYS_MISMATCH_OF_AC_AND_DC_POWER,4,交直流功率不匹配,AC Power Mismatch A_PCS_FAULT_SYS_RS485_COMMUNICATION_FAULT,4,RS485通信故障,RS485 Communication Fault A_PCS_FAULT_SYS_OTHER_FAULT,4,其他未知故障,Other System Fault # 电表告警信息 A_EMT_GRID_OFFLINE,4,电网电表离线,Grid Meter Offline A_EMT_EMS_OFFLINE,4,储能电表离线,Energy Storage Meter Offline A_EMT_EPV_OFFLINE,4,光伏电表离线,PV Meter Offline A_EMT_LOAD_OFFLINE,4,负载电表离线,Load Meter Offline # PV告警信息 A_PV_OFFLINE,4,离线,Offline # PVDC告警信息 A_PVDC_OFFLINE,4,离线,Offline A_PVDC_ALARM_DCDC_TEMPERATURE_HIGH,4,DCDC温度过高,DC/DC module overtemperature A_PVDC_HW_FAULT_EPO_EMERGENCY_POWER_OFF,4,紧急断电(EPO)故障,Emergency Power-Off (EPO) fault A_PVDC_HW_FAULT_IGBT_OCP_OVER_CURRENT_PROTECTION,4,IGBT过流保护(OCP)故障,IGBT hardware overcurrent (OCP) A_PVDC_HW_FAULT_HIGH_SIDE_HARDWARE_OVER_VOLT,4,高压侧硬件过压故障,High-side hardware overvoltage A_PVDC_HW_FAULT_HIGH_SIDE_HARDWARE_OVER_CURRENT,4,高压侧硬件过流故障,High-Side hardware overvoltage A_PVDC_HW_FAULT_IGBT_HARDWARE_OVER_CURRENT,4,IGBT硬件过流故障,IGBT hardware overcurrent A_PVDC_HW_FAULT_DC24V,4,DC24V电源故障,DC24V power fault A_PVDC_HW_FAULT_FAN,4,风扇故障,Fan fault A_PVDC_HW_FAULT_SINGLE_BOARD_CONNECTION,4,单板连接故障,Single board connection fault A_PVDC_HW_FAULT_POWER_MODULE_OVER_TEMPERATURE,4,功率模块过温故障,Power module overtemperature A_PVDC_HW_FAULT_PN15V_AUXILIARY_POWER,4,±15V 辅源故障,±15V auxiliary power fault A_PVDC_HW_FAULT_INTERNAL_FAULT_ALL,4,内部故障,Internal fault A_PVDC_DCDC_FAULT_PRE_CHARGE_TIMEOUT,4,预充超时,Pre-charge timeout A_PVDC_DCDC_FAULT_LV_PHASE_A_SW_OVERCURRENT,4,低压侧A相软件过流,Low voltage side phase A switch overcurrent A_PVDC_DCDC_FAULT_LV_PHASE_B_SW_OVERCURRENT,4,低压侧B相软件过流,Low voltage side phase B switch overcurrent A_PVDC_DCDC_FAULT_LV_PHASE_C_SW_OVERCURRENT,4,低压侧C相软件过流,Low voltage side phase C switch overcurrent A_PVDC_DCDC_FAULT_LV_NEGATIVE_SW_OVERCURRENT,4,低压侧负极软件过流,Low voltage side negative switch overcurrent A_PVDC_DCDC_FAULT_MODULE_INTERNAL_SHORT_CIRCUIT,4,模块内部短路,Module internal short circuit A_PVDC_HVLV_FAULT_HV_PRE_CHARGE_OVERVOLTAGE,4,高压侧预充过压,High voltage side pre-charge overvoltage A_PVDC_HVLV_FAULT_HV_REVERSE_POLARITY,4,高压侧极性反接,High voltage side reverse polarity A_PVDC_HVLV_FAULT_HV_SHORT_CIRCUIT,4,高压侧短路,High voltage side short circuit A_PVDC_HVLV_FAULT_HV_OPERATING_OVERVOLTAGE,4,高压侧运行过压,High voltage side operating overvoltage A_PVDC_HVLV_FAULT_HV_OPERATING_UNDERVOLTAGE,4,高压侧运行欠压,High voltage side operating undervoltage A_PVDC_HVLV_FAULT_HV_BUS_IMBALANCE,4,高压侧母线不平衡,High voltage side bus imbalance A_PVDC_HVLV_FAULT_INSULATION_RESISTANCE_LOW,4,绝缘电阻低,Insulation resistance low A_PVDC_HVLV_FAULT_LOW_VOLTAGE_UNDERVOLTAGE,4,低压侧欠压,Low voltage side undervoltage A_PVDC_HVLV_FAULT_SOFTWARE_TRANSIENT_OVERCURRENT,4,软件瞬时过流,Software transient overcurrent A_PVDC_HVLV_FAULT_LOW_VOLTAGE_OVERVOLTAGE,4,低压侧过压,Low voltage side overvoltage A_PVDC_HVLV_FAULT_LOW_VOLTAGE_OVERCURRENT,4,低压侧过流,Low voltage side overcurrent A_PVDC_HVLV_FAULT_LOW_VOLTAGE_REVERSE_POLARITY,4,低压侧极性反接,Low voltage side reverse polarity A_PVDC_SYS_FAULT_CONTROL_BOARD_EEPROM,4,控制板EEPROM故障,Control board EEPROM fault A_PVDC_SYS_FAULT_SLAVE_CAN_COMMUNICATION,4,从机CAN通信故障,Slave CAN communication fault A_PVDC_SYS_FAULT_EMS_COMMUNICATION,4,EMS通信故障,EMS communication fault A_PVDC_SYS_FAULT_SW_DETECTED_INPUT_OVERVOLTAGE,4,软件检测输入过压,Software detection input overvoltage A_PVDC_SYS_FAULT_SW_DETECTED_INPUT_UNDERVOLTAGE,4,软件检测输入欠压,Software detection input undervoltage A_PVDC_SYS_FAULT_SW_DETECTED_INPUT_OVERCURRENT,4,软件检测输入过流,Software detection input overcurrent A_PVDC_SYS_FAULT_SW_DETECTED_OUTPUT_OEVERCURRENT,4,软件检测输出过流,Software detection output overcurrent A_PVDC_SYS_FAULT_SW_DETECTED_INPUT_OVERVOLTAGE_FAULT,4,软件检测输入过压故障,Software detection input overvoltage fault A_PVDC_SYS_FAULT_SW_DETECTED_INPUT_UNDERVOLTAGE_FAULT,4,软件检测输入欠压故障,Software detection input undervoltage fault A_PVDC_SYS_FAULT_HOST_MODE_MISMATCH,4,主机模式不匹配,Host mode mismatch